Signet has combined the 9900 SmartPro® Transmitter with the 515/8510 and 2536/8512 Paddlewheel Flow sensors to create integral systems that are easy to order and simple to install. Integral systems are also available in conductivity, level, temperature, and pressure configurations.

Each integral system features a 9900 Transmitter which provides a local and easy to read LCD display. The push button keypad makes it easy to navigate through the transmitter’s menu. The DC-powered 9900 features a scalable 4 to 20 mA output and open collector for process control.

Flow Integral Systems with 9900 Transmitters are combined with Signet’s field-proven Models 515/8510 and 2536/8512. These sensors reliably perform in flow ranges from 0.3 to 6 m/s (1 to 20 ft/s) and 0.1 to 6 m/s (0.3 to 20 ft/s) respectively for pipe sizes from ½ to 8 inches. They are available in a variety of materials including polypropylene and PVDF and are easily mounted in the pipe using Signet’s comprehensive line of standard fittings.

Paddle wheel Flow meter Features

  • Warning LED indicator
  • Selectable error mode for current outputs, 3.6 mA or 22 mA
  • Large auto-sensing backlit display with “at a glance” visibility
  • Local display for sensor mounted instruments
  • Provides 4 to 20 mA output
  • “Dial-type” digital bar graph
  • NEMA 4X/IP65

Description

General
Input Channels One
Input Types Digital (S3L) Serial ASCII, TTL level, 9600 bps
Frequency Range 0.5 to 1500 Hz
Accuracy 0.5% of reading
Measurement Types Flow, pH/ORP, Conductivity/Resistivity, Salinity, Pressure, Temperature, Level, Dissolved Oxygen, Batch or user-de?ned (via 8058)
Enclosure and Display
Case Material PBT
Window Shatter-resistant glass
Keypad 4 buttons, injection-molded silicone rubber seal
Display Backlit, 7 and 14-segment
Update Rate 1 s
LCD Contrast 5 settings
Indicators ?Dial-type? digital bar graph. LEDs for Open Collector, Relays and Warning Indicator
Enclosure Size ¼ DIN
Mounting 9900-1P
Panel ¼ DIN, ribbed on four sides for panel mounting clip inside panel, silicon gasket included. Optional rear enclosure with ?at cover available for waterproof protection when installed inside a panel.
Wall Options include 9900-1P installed in pre-wired NEMA enclosure or inside of rear enclosure with hinged cover.
Pipe Optional Rear Enclosure with hinged cover and 9900-1P for pipe mount installation
Mounting 9900-1
Field (Integral) Options include yellow universal or integral kits for installation with sensor
Display Ranges
pH 0.00 to 15.00 pH
pH Temperature -39.99 °C to 149.99 °C -40 °F to 302 °F
ORP -1999 to +1999 mV
Flow Rate -9999 to 99999 units per second, minute, hour or day
Totalizer 0.00 to 99999999 units
Conductivity 0.0000 to 99999 ?S, mS, PPM and PPB (TDS), k?, M?
Conductivity Temperature -100 °C to 250 °C ?148 °F to 350 °F (application and sensor dependent)
Temperature -99 °C to 350 °C ?99 °F to 350 °F
Pressure -40 to 1000 psi
Level -9999 to 99999 m, cm, ft, in, %
Volume 0 to 99999 cm3, m3, in3, ft3, gal, L, lb, kg, %
Salinity 0 to 99.97 PPT
Dissolved Oxygen PPM 0-50, % SAT 0-200, 0 to 999.9 TORR
Dissolved Oxygen Temperature -99 °C to 350 °C ?99 °F to 350 °F
Environmental

Ambient Operating Temperature

Backlit LCD -10 °C to 70 °C 14 °F to 158 °F
Storage Temperature -15 °C to 70 °C 5 °F to 158 °F
Relative Humidity 0 to 100% condensing for ?eld mount; 0 to 95% non-condensing for panel mount
Maximum Altitude 4,000 m (13,123 ft)
Enclosure Rating NEMA 4X/IP65 (front face only on panel mount); ?eld mount is 100% NEMA 4X/IP65

Electrical Requirements Power to Sensors

Voltage +4.9 to 5.5 VDC @ 25 °C, regulated
Current 1.5 mA max in loop power mode (up to 2.0 mA with 24 V @ 300 ? max. loop impedance); 20 mA max when using DC power
Short Circuit Protected
Isolation Low voltage (< 48V AC/DC) to loop with DC power connected

No isolation when using loop power only

Terminal Blocks Pluggable screw type 14 AWG max wire gauge
Input Power
DC 10.8 to 35.2 VDC, regulated
9900 without Relay Module 200 mA @ 10.8 VDC to 35.2 VDC
9900 with Relay Module 300 mA @ 10.8 VDC to 35.2 VDC
Overvoltage Protection 48 Volt Transient Protection Device

Current limiting for circuit protection Reverse-Voltage Protection Loop Power No DC Power Input

Max. Loop Impedance 50 ? @ 12 V 325 ? @ 18 V 600 ? @ 24 V

With DC Power Input or with 2nd loop, all the time

Max. Loop Impedance 250 Ω@ 12 V 500 Ω @ 18 V 750 Ω @ 24 V
Relay Speci?cations
Dry-Contact Relays (2) Open Collector (1)
Type SPDT N/A
Form C N/A
Max. Current Rating 5 A resistive 50 mA DC
Max. Voltage Rating 30 VDC or 250 VAC 30 VDC
Hysteresis Adjustable (absolute in engineering units) (EUs)
Latch Reset in test screen only
Delay 9999.9 seconds (max.)
Test Mode Set On or Off
Cycle Time 99999 seconds (max.)
Maximum Pulse Rate 300 pulses/minute
Proportional Pulse 400 pulses/minute
Volumetric Pulse Width 0.1 to 3200 s
Pulse Width Modulation 0.1 to 320 s
Input Types

Digital (S3L) or AC frequency4 to 20 mA input via the 8058-1pH/ORP input via the Digital (S3L) output from the 2750/2751 pH/ORP Sensor ElectronicsRaw Conductivity/Resistivity input directly from Signet Conductivity/Resistivity electrodes via Direct Conductivity/ Resistivity Module or via 2850

Input Speci?cations
Digital (S3L) Serial ACSII, TTL level, 9600 bps

Frequency Input

Sensitivity 80 mV @ 5 Hz, gradually increasing with frequency
Span 0.5 Hz to 1500 Hz @ TTL level input
Accuracy ± 0.5% or reading max error @ 25 °C
Resolution 1 ?S
Repeatability ± 0.2% of reading

Speci?cations (continued)Input Speci?cation continued Power Supply

Rejection ±1 ?A per volt
Short Circuit Protected
Update Rate (1/frequency) + 150 ms
Output Speci?cations

Current Output – One (1); Two (2) with 4 to 20 mA Output Module

Current Loop Output Standard ANSI-ISA 50.00.01 Class H
Current Output 4 to 20 mA, isolated, fully adjustable and reversible
Span 3.8 to 21 mA
Zero 4.0 mA factory set; user programmable from 3.8 to 5.0 mA
Full Scale 20.00 mA factory set; user programmable from 19.0 to 21.0 mA
Accuracy ±32 ?A max. error @ 25 °C @ 24 VDC
Resolution 6 ?A or better
Temperature Drift ±1 ?A per °C
Power Supply Rejection ±1 ?A per V
Isolation Low voltage (< 48 VAC/DC)
Voltage 12 to 32 VDC ±10%
Max. Impedance (with DC power input) 250 Ω @ 12 VDC 500 Ω @ 18 VDC 750 Ω @ 24 VDC
Max. Impedance (no DC power input) 50 Ω @ 12 VDC 325 Ω @ 18 VDC 600 Ω @ 24 VDC
Update Rate 150 mS nominal
Short circuit and reverse polarity protected
Adjustable Span Reversible
Error Condition Selectable error condition 3.6 or 22 mA
Actual update rate determined by sensor type
Test Mode Increment to desired current (range 3.8 to 21.00 mA)
Shipping Weights
Base Unit 0.63 kg 1.38 lb
Modbus Module 0.16 kg 0.35 lb
H COMM Module 0.16 kg 0.35 lb
Conductivity Module 0.16 kg 0.35 lb
Relay Module 0.19 kg 0.41 lb
Batch Module 0.16 kg 0.35 lb
4 to 20 Output Module 0.16 kg 0.35 lb
Rear Enclosure, Hinged cover 0.30 kg 0.65 lb
Rear Enclosure, Flat cover 0.28 kg 0.60 lb
Standards and Approvals
CE, UL, CUL, FCC
RoHS Compliant, China RoHS
Lloyd?s Register
Manufactured under ISO 9001 and ISO 14001 for Environmental Management and OHSAS 18001 for Occupational Health and Safety

Refer to Models 515/8510, 2536/8512 and 9900 technical specifications for more details on these products

MFR # Pipe Size(inch) Code Pin / Body
3-9900-1 w/ 3-8510-P0 0.5 – 4.0 159001733 Titanium/ PP
3-9900-1 w/ 3-8510-H0 0.5 – 4.0 159001734 Hastelloy-C / PP
3-9900-1 w/ 3-8510-S0 0.5 – 4.0 159001735 Natural PVDF / PP
3-9900-1 w/ 3-8510-V0 0.5 – 4.0 Special via DZS Hastelloy-C / Natural PVDF
3-9900-1 w/ 3-8510-T0 0.5 – 4.0 159001736 Natural PVDF ; Natural PVDF
3-9900-1 w/ 3-8510-P1 5.0 to 8.0 159001737 Titanium / PP
3-9900-1 w/ 3-8512-P0 0.5 – 4.0 159001738 Titanium / PP
3-9900-1 w/ 3-8512-H0 0.5 – 4.0 159001739 Hastelloy-C / PP
3-9900-1 w/ 3-8512-S0 0.5 – 4.0 159001740 Natural PVDF / PP
3-9900-1 w/ 3-8512-V0 0.5 – 4.0 159001741 Hastelloy-C / Natural PVDF
3-9900-1 w/ 3-8512-T0 0.5 – 4.0 159001742 Natural PVDF / Natural PVDF
3-9900-1 w/ 3-8512-P1 5.0 to 8.0 159001743 Titanium / PP

Brand

Georg Fischer

georg Fischer Signet logo

Additional information

Options

Integral 3-9900-1 w/ 3-8510-P0, Integral 3-9900-1 w/ 3-8510-H0, Integral 3-9900-1 w/ 3-8510-S0, Integral 3-9900-1 w/ 3-8510-T0, Integral 3-9900-1 w/ 3-8510-P1, Integral 3-9900-1 w/ 3-8512-P0, Integral 3-9900-1 w/ 3-8512-H0, Integral 3-9900-1 w/ 3-8512-S0, Integral 3-9900-1 w/ 3-8512-V0, Integral 3-9900-1 w/ 3-8512-T0, Integral 3-9900-1 w/ 3-8512-P1, Integral 3-9900-1 w/ 3-2450-2H, Integral 3-9900-1 w/ 3-2350-1