Radar Continuous Level Measurement | GF2291

Radar Continuous Level Measurement | GF2291

Radar Continuous Level Measurement – Overview

This Radar level transmitter is designed for continuous level measuring of conductive or non-conductive liquids, pulps and solids. It operates based on the Time Domain Reflectometry principle. Micropulses are sent along a probe guide at the speed of light. As soon as the impulse reaches the surface of the medium, it is reflected back to the electronic module. Level distance is directly proportional to the flight time of the impulse. The reflected signal is dependent on the dielectric constant of the material; the feasibility of the measurement is εr ≥ 1.9. The TDR technology is unaffected by the properties of the medium as well as that of the space above it. Measurement is also unaffected by the change in the physical properties of the materials such as temperature, pressure, and dielectric constant. It’s reliability and precise measurements are useful in challenging conditions like agitated liquids, aggressive media, heavy chemical fumes, pressurized tanks or foam. Easy installation is ensured as you enter the basic tank parameters via the transmitters HMI or the GF Eview software and then the device configuration is completed. Secure and fast mounting of the devices is enabled by multiple options for process connection and coatings. Its superb durability is a result of high-performance coatings that protect the contacting probes in harsh conditions, ensuring even greater reliability.

Radar Continuous Level Measurement – Features

  • Safe and reliable
  • East to install
  • Superb durability
  • Measuring range up to 6 m
  • Accuracy: ± 5 mm
  • PP / PFA coated probes available on request
  • Rod & cable versions available
  • Minimum εr 1.9
  • 2-wire version
  • Graphic LCD display
  • 4 to 20 mA + HART output
  • Medium temperature range: -30 °C to +90°C
  • Maximum process pressure: 40 bar
  • IP67 protection

Description

Radar Continuous Level Measurement | GF2291

General
Measured Values Level, Distance; Calculated values: Volume, Mass
Measuring Range Depends on the probe type and dielectric constant (εr ) of the measured medium
Probe Types Mono cable, mono rod
Accuracy: Linearity Error¹ For liquids: ± 5 mm (0.2 in.), if probe length ± 10 m (32 ft): ± 0.05 % of the probe length
Accuracy: Resolution ± 3 µA
Minimal εr of the Medium 1.9
Power Supply 18 V… 35 V DC
Output: Digital Communication 4 to 20 mA + HART
Output: Display Graphical LCD display unit
Medium Temperature -30 °C… +90 °C (-22 °F… +194 °F),
Maximum Medium Pressure 4 MPa (40 bar g/ 580 psi g); with plastic lined flange: max. 2.5 MPa (25 bar g/ 363 psi g)
Ambient Temperature -20 °C… +60 °C (-4 °F… +140 °F)
Process Connection 1 in. BSP, 1 in. NPT Thread
Ingress Protection IP 67
Electrical Connection 2x M20x1.5 cable glands + internal thread for 2x ½ in. NPT cable protective pipe, cable outer diameter: Ø 7 … Ø 13 mm (0.3 … 0.5 in.), wire cross-section: max. 1.5 mm2 (AWG 15)
Electrical Protection Class III
Housing Material Plastic (PBT)
Sealing FKM, On request: FFKM, EPDM
Mass (head unit) 1.5 kg (3.3 lb)
EX-Approvals ATEX (ia): II 1/2 G Ex ia IIB T6…T5 Ga/Gb
ICEX (ia): EX ia IIB T6…T5 Ga/Gb

¹ Under reference conditions and stabilised temperature

Radar Continuous Level Measurement | GF2291

Brand

Georg Fischer

georg Fischer Signet logo

Reviews

There are no reviews yet.

Be the first to review “Radar Continuous Level Measurement | GF2291”