Non-contact Radar Level Transmitter | GF 2298

Non-contact Radar Level Transmitter | GF 2298

Non-contact Radar Level Transmitter  – Overview

This rugged, high-performance radar level measurement sensor has a transducer and processing electronics incorporated in one. It is suitable for single and multiple-tank applications. 2-wire sensors are recommended using either HART protocol or 4 to 20 mA for direct communication with a panel mount controller or a PLC. This is used for liquid level measurement in sumps or tanks, for tank volume measurement, or open channel flow measurement. Sensing ranges up to 20 m (66 ft) are available. PP and PVDF sensor bodies provide the best chemical resistance in applications where concentrated chemicals need to be detected. Applications include Water Treatment, Corrosive Industrial Waste Treatment, Filling, Batching, Bulk Transfer, and Dirty Liquids.

Non-contact Radar Level Transmitter  – Features

  • 2-wire compact sensor
  • Compatible with 9900 Sensor (optional signal converter)
  • Non-contact level measuring
  • Narrow 7° beam angle
  • Level, volume and open channel flow
  • Compact housing
  • Fully temperature-compensated electronics
  • Outstanding signal processing software providing highly accurate measuring results
  • Chemical resistance – PP or PVDF sensor body
  • Secondary lightning protection
  • 4 to 20 mA / HART interface

Description

Non-contact Radar Level Transmitter | GF 2298

Specifications
Antenna type
Encapsulated Antenna
Antenna size ⌀1″ * ⌀1½”
Dead zone (1) 0 m (0 ft)
Max. measuring distance (2) 10 m 10 m 20 m
Antenna insertion length (3) 56 mm 70 mm 70 mm
Accuracy (4) ±5 mm ±5 mm ±2 mm
Process pressure
–1…3 bar (–14.5…43.5 psi)
Beam angle (–3 dB) 12°
Process connection 1″ BSP / NPT 1½” BSP / NPT 1½” BSP / NPT
Materials Housing
PP, PVDF, PTFE*
Materials Seal EPDM
Materials Cable
Cable sealing: EPDM, cable isolation: PVC
Measured Values
Level, Distance; Calculated values: Volume, Mass
Frequency of the Measuring Signal
~80 GHz (W-band)
Linearity Error (as per EN 61298-2) See diagram
Minimum dielectric constant εr of the Medium
1.9 ( refer to diagram)
Resolution
0.1 mm (0.0039“)
Power Supply Voltage 12…36 V DC
Output Digital Communication
4…20 mA; (3.9…20.5 mA); RLmax = (US – 12 V) / 0.02 A + HART
Measuring Frequency ~1/s
Antenna Diameter
1“ (25.4 mm); 1½“ (38.1 mm)
Antenna Material
Horn: Stainless Steel; enclosure: PP / PVDF / PTFE
Medium Process Temperature PVDF: –40…+80 °C
PP: –30…+80 °C
Ambient Temperature PVDF: –40…+80 °C
PP: –30…+80 °C
Upper process connection 1“ BSP
Protection class IP66 / IP68
Electrical Connection (5)
4 × 0.5 mm2 shielded Ø6 mm cable × 5 m (up to 30 m); (4 × 22 AWG shielded Ø0.24“ cable × 16.4 ft [up to 98.5 ft]); For the relay option: 7 × 0.5 mm2 (22 AWG) shielded cable
Electrical Protection
Class I overvoltage protection; (Class III [SELV])
Communication Certifications R&TTE, FCC
Weight ~600 g (1.3 lb)
Standards and Approvals
Directive 2014/35/EU (LVD), Directive 2014/30/EU (EMC), Directive 2014/53/EU (RED), Directive 2015/863/EU (RoHS 3)

*Available on request.

(1) From the tip of the antenna, if dielectric constant (εr) < 80.

(2) May be limited for media with low dielectric constants or non-vertical or non-planar surfaces.

(3) From process connection.

(4) With an ideal reflecting surface, according to IEC 62828-1, an accuracy of ±2 mm (±0.079») is not guaranteed for Region 3 and Region 4 settings.

(5) Operate only with galvanically isolated power supply!